工艺控制及测量
新产品
SLA2X
    发布时间: 2017-11-28 11:52    

SLA2X is an unit suitable for the connection with capacitance and ultrasonic level transmitter. It display the input analog variable and depending of model, it can provide 2 or 4 relays. Each threshold can be programmed with different kinds of hysteresis. Two analog exit 0÷10V and 4÷20mA, and RS232 or MODBUS serial port are available again depending of the model. Designed to be mached with 4-20mA transmitter, it is specially used to be directly connected to TC22, TC26 e TC30 capacitance level transmitter, furthermore the ultrasonic transmitters 2-wire METER can be powered directly from the SLA2X. A special function allows a remote self-calibration facility; it can memorized empty-situation by press a pushbutton and the level-condition (from 20 to 100%) pressing another pushbutton. This function can help during the calibration when using capacitance transmitter and is not easy to change the level from 0 to 100% as riquired from capacitance transmitter. The level measurement can be converted into volumes or weights, and an optional linearization system can convert to engineering units a level not commensurate with the volume. 

· Suitable for any transmitter 4-20mA

· Wide versions range

· Front panel mounting (std.)

· 24Vdc, 24/115/230/Vac power supply

· IP40 or IP54 or IP66 mechanical proof


SLA2X
Case
panel mount 48x96 frontal IP40; frontal windows IP54; wall mounting execution IP66
Case material Noryl
Keyboard
4 membrane pushbuttons
Display
5+1 digit, max displayed value +-99999
LEDs 4 red
Connections
2 terminal strips, 12 pole
Power supply
24 115 230Vca, 24Vdc; ±10% depending on model
Power consumption 3,3VA (3W)
Measuring input
4÷20mA Ri = 100ohm
Self-calibration input IN1, IN2 max 18Vdc, 4mA
Data memory
EEPROM
Transmitter supply output 24Vdc-45mA max
Alarm limits (opt.)
2 or 4 with relays depending on model
Relays rating (opt.) 5A 250V
Analog exit (opt.)
0÷10V (min.1Kohm) o 4÷20mA (max.500ohm)
Serial port (opt.)
RS232 or MODBUS
Converter resolution
±20000 punti
Linearity 0,0025%
Operating temperature
-10°C ÷ +50°C
Conformity to CEE guidelines 93/68 CEE

Manuale Operativo

Operating Manual